Configuration parameters of the "CAN Bus" sub-menu of the "Networks" menu
The following table shows the meaning of the configuration parameters of the "CAN Network" section of the "CAN Bus" sub-menu or the
"Networks" menu.
PARAM.
MIN.
MAX.
M. U.
DEF.
DESCRIPTION
MyNode
1
127
- - -
1
local CAN node or device address
Master
- - -
- - -
- - -
YES
enabled to function as master in a CAN network
YES
=
yes
Baud
- - -
- - -
- - -
20K
baud rate of the CAN-type communication
20K
=
20.000 baud
50K
=
50.000 baud
125K
=
125.000 baud
500K
=
500.000 baud
Timeout
1
60
s
5
remote CAN-type communication timeout, i.e., communication
with the other network elements (after the time set with this
parameter has elapsed with no CAN-type communication with an
element, the element is disabled).
Network
Node
[1] 0
[32] 127
- - -
[1] 99
address of the CAN nodes or of the other network elements (e.g.
for [1] 2)
[1]
=
node
2
=
node address
TSEG1
- - -
- - -
- - -
- - -
reserved
TSEG2
- - -
- - -
- - -
- - -
reserved
SJW
- - -
- - -
- - -
- - -
reserved
BTR
- - -
- - -
- - -
- - -
reserved
Status
parameter available in read-only mode
CAN machine status
INIT
=
initialisation
STOPPED
=
stop CAN
OPERAT
=
operating
PRE-OP
=
in pre-operating mode
Bus Status
parameter available in read-only mode
CAN bus status
OK
=
status OK
WARNING
=
attention
PASSIVE
=
bus in receiving mode only
BUS OFF
=
bus stopped
Cnt Rx
parameter available in read-only mode
number of packets received