Sauter Italia S.p.A.
RDT921F901
| Hardware manual ver. 1.0 | Code 114RDT921E104SAU
page 31 of 38
7
TECHNICAL DATA
7.1
Technical data
Purpose of the command device:
operating command device.
Construction of the command
device:
built-in electronic device.
Container:
grey self-extinguishing.
Heat and fire protection class:
D.
Dimensions:
142.0 x 128.0 x 60.0 mm (5.590 x 5.039 x 2.362 in; L x H x D); 8 DIN modules
The dimensions refer to the device with all the screw-in removable terminal boards in place.
Method
of
mounting
the
command device:
on a DIN 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in), track in
a control panel.
Protection grade:
-
IP20 overall
-
IP40 for the front.
Connections
-
screw in removable terminal board, male only 3,5 mm pitch (0,137 in) for wires
up to 1,5 mm² (0,0028 in²): power supply, analog inputs, digital inputs, analog
outputs and ports RS-485 MODBUS slave, RS-485 MODBUS master/slave and
CAN CANBUS
-
screw in removable terminal board, male only 5 mm pitch (0,196 in) for wires
up to 2,5 mm² (0,0038 in²): digital outputs
-
type A USB connector: USB port
-
RJ45 F phone connector: MODBUS TCP, Web Server, BACnet IP Ethernet port.