Sauter Italia S.p.A.
RDT921F901
| Hardware manual ver. 1.0 | Code 114RDT921E104SAU
page 32 of 38
The maximum lengths of the connection cables are:
-
power supply: 100 m (328 ft)
-
analog inputs: 100 m (328 ft)
-
transducers power supply: 100 m (328 ft)
-
digital inputs: 100 m (328 ft)
-
analog outputs PWM: 1 m (3.280 ft)
-
analog outputs 0-20 mA, 4-20 mA and 0-10 V: 100 m (328 ft)
-
digital outputs (electromechanical relay): 100 m (328 ft)
-
digital outputs (controls for solid state relays) 100 m (328 ft)
-
RS-485 MODBUS slave and RS-485 MODBUS master/slave ports: 1,000 m
(3,280 ft); please refer also to the
MODBUS specifications and implementation
guides
available at http://www.modbus.org/specs.php
-
CAN CANBUS port:
-
1.000 m (3.280 ft) with baud rate 20.000 baud
-
500 m (1.640 ft) with baud rate 50.000 baud
-
250 m (820 ft) with baud rate 125.000 baud
-
50 m (164 ft) with baud rate 500.000 baud
-
USB port: 1 m (3.280 ft)
To wire the device, the use of the CJAV31 kit (to be ordered separately) is recommended:
screw-in removable terminal boards, female only, 3.5 mm pitch (0.137 in) for wires up to
1.5 mm² (0,0028 in²) and screw-in removable terminal boards, female only, 5 mm pitch
(0.196 in) for wires up to 2.5 mm² (0,0038 in²) .
To program the device, the use of the 0810500018 or 0810500020 connection cables (to be
ordered separately) s recommended: the 0810500018 cable is 2.0 m (6.56 ft) long , the
0810500020 cable is 0.5 m (1.640 ft) long.)
Operating temperature:
-
from -10 to 55 °C (from 14 to 131 °F) for the built-in models
-
from -20 to 55 °C (from -4 to 131 °F) for the blind models
Storage temperature:
from -25 to 70 °C (from -13 to 158 °F).
Humidity for use:
from 10 to 90 % relative humidity without condensate.
Command
device
pollution
situation:
2.
Height at which it is used:
from 0 to 2,000 m (from 0 to 6,591 ft).
Height at which it can be
transported:
from 0 to 3,048 m (from 0 to 10,000 ft).
Environmental standards:
-
RoHS 2011/65/CE
-
WEEE 2012/19/EU
-
REACH (CE) regulation n. 1907/2006.
EMC standards:
-
EN 60730-1
-
IEC 60730-1.