7. Define whether detector presence is to be monitored (
- yes,
- no) and press
the
button.
6.8.2 Using MTX soft program
1. Click on the “Detectors” tab.
2. Click on the detector you want to configure.
3. Click on the
button, “Output” column. Context menu will be displayed.
4. Select the output and define how it is to respond to detector violation (ON – output will be
on, OFF – output will be off, BI – output status will change to opposite, Mono – output will
be on for indicated period of time (if you select “PULSE”, the output will be on as long as
the detector is violated)).
5. Double click on the field in “Presence c.” column to enable / disable detector presence
control (symbol “x” indicates that the control is enabled).
6.9 Configuring sirens
Define for a newly added siren:
which controller inputs will trigger signaling,
whether the controller is to supervise the siren presence,
maximum signaling time.
6.9.1 Using controller buttons
1. Run the
function.
2. Select the siren to be configured and press the
button.
3. Run the
function and then the
function.
4. Select the input which is to trigger signaling (
- none, - input IN1,
- input IN2,
- inputs IN1 and IN2) and then press the
button.
5. Run the
function.
6. Define whether siren presence is to be controlled (
- yes,
- no) and press the
button.
6.9.2 Using MTX soft program
1. Click on the “Inputs/sirens” tab.
2. Click on the selected siren.
3. Double click on the field in the “IN1” column to define whether the input IN1 is to trigger
signaling or not (symbol “x” means that the input will trigger signaling).
4. Double click on the field in the “IN2” column to define whether the input IN2 is to trigger
signaling or not (symbol “x” means that the input will trigger signaling).
5. Enter the maximum signaling time in the “Time” column.
6. Double click on the field in the “Presence c.” column to enable / disable the siren
presence control (symbol “x” means that the control is enabled).
6.10 Programming signaling parameters
The signaling parameters (signaling method, signaling priority) should be defined when
configuring the inputs. Each of the controller inputs may trigger different type of signaling.