12
Step #3:
Connect Push Plates and Locking Devices as shown below.
Note: An electric strike could be wired in place of a 56-Latch Retraction Exit Device.
External Wiring: 56-80 Series Exit Device
FUSE
LINE
NEUTRAL
GROUND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
NON DELAYED IMPULSE INHIBIT
COMMON
SAFETY SENSOR
COMMON
DELAYED IMPULSE
COMMON
NON DELAYED IMPULSE
COMMON
LOCKING CIRCUIT
N.O.
RELAY
COM OUTPUT
N.C.
GND
+12 VDC
GND
+24 VDC
BROWN WIRE
SELECT
JUMPER
JUMPER
PUSH PLATE
PUSH PLATE
56-80 SERIES
EXIT DEVICE
BLACK
RED
230 VAC
115 VAC
Operation Description: The push plate signals the 2600 door operator which retracts the latchbolt(s) of exit device
after a field adjustable preset delay on the operator, the door will open.
External Connections
External Connections are connections to remote equipment. For example, a switch, sensor, or latch retraction exit
device.
Only voltage-free (dry contact) switches can be used to control the SARGENT 2600 Series Low-Energy Swing Door
Operator. The total resistance of the control switch and its wiring must not exceed 100 ohms when the switch is
closed.
Connections include a program selector, a normal or delayed pulse, and a locking circuit connection. One of the
wires running to the switch c5V and the other the ground level of the Control Unity, when the switch is open.
INITIAL ELECTRICAL CONNECTIONS