21
Control Value
Factory
Point Description
Range
Setting
Comments
Number
05
Opening speed
1 – 10
4
The speed at which the door moves from fully
relative
closed to back check.
1 = minimum speed
10 = maximum speed
• Opening speed affects obstruction sensitivity;
see Control Point 12.
06
Back check speed
1 – 10
4
The speed at which the door moves from back
relative
check to fully open.
1 = minimum speed
10 = maximum speed
• Back check speed must be slower than
opening speed.
• The Operator is not a door stop. Install a door
stop to prevent damage to wall or Operator.
07
Door hold open time:
0 – 60
15
The time the door is held at the fully open
Non delayed impulse
sec
position when activated by an non delayed
impulse (for example, a push plate).
• Door opening time starts when the door reaches
fully open position.
08
Operator acceleration
1 – 10
4
This setting controls how quickly the Operator
time Sealed
relative
causes the door to accelerate.
Control Point
1 = minimum acceleration time (slower)
10 = maximum acceleration time (faster)
• See Control Points Affecting Speed and Closing.
Note: Don’t accelerate too fast.
09
Closing speed
1 – 5
3
The speed at which the door moves from the
relative
fully open position to the latching speed starting
point.
1 = minimum speed
5 = maximum speed
• Closing speed should be slower than opening
speed.
• See Control Points Affecting Speed and Closure.
10
Latching speed
1 – 3
3
The speed at which the door moves from latching
relative
speed starting point to fully closed.
1 = minimum speed
3 = maximum speed
• Latching speed must be equal to or slower
than closing speed.
• See Control Points Affecting Speed and
Closure.
WARNING:
LATCHING SPEED MUST BE SUCH
THAT THE DOOR TAKES AT LEAST 1.5 SEC TO
MOVE FROM LATCHING SPEED STARTING
POINT TO FULLY CLOSED.
CONTROL POINTS