Double Mount Installation
1) Install the double gang box in the wall or ceiling.
If you are installing the gang box in the wall, leave at
least eleven inches between the top of the gang box
and the ceiling. If you are installing the gang box in
the ceiling, leave at least eleven inches between the
gang box and the wall. The box should be installed
level and plumb with the wall and ceiling.
3) Detach the mounting plate from the mounting
pole by unscrewing the two screws. Set the screws
and pole aside for later.
4) Attach the mounting plate to the gang box using
only two of the four long, silver #6-32x1 screws.
With the mounting plate as a guide, use the pencil
to trace the locations of the four larger holes at the
outer corners.
Ceiling
11” Minimum
2) Run a CAT5 or CAT6 data cable from a PoE
switch or PoE injector to the gang box. Confirm that
the switch or injector, and either an NTP server or
internet modem, are connected to your network
router. The clock-side of the cable should terminate
in a male RJ45 connector.
KNOW YOUR NETWORK
Make sure that your network firewall is set to
allow communication between the clocks and
NTP servers. This means that Ports 80, 123,
and 1777 must be open.