8-1. Room Temperature Control
■
Cooling
●
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room tem-
perature sensor in the remote control unit.
●
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the
controller in the indoor unit.
●
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least
3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pres-
sure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
●
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor
operation.
●
Thermo. ON : When the room temperature is above T + 2°F (T°C is set temperature).
Compressor
➞
ON
●
Thermo. OFF : When the room temperature is equal to or below set temperature T°F.
Compressor
➞
OFF
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
5 minutes
ON
OFF
ON
OFF
ON
OFF
Compressor
ON
OFF
ON
OFF
ON
OFF
More than
5 minutes
Outdoor fan
Indoor fan
Set speed
T + 2
¡
F
T
¡
F
set temp.
Thermo.
OFF
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
Thermo.
ON
Thermo.
ON
Thermo.
ON
Room temp.
Signal from remote control unit
000-111
SM
(18-68)
00.3.17
11:49
AM
y [ W 47
Summary of Contents for CH0951
Page 41: ...37 5 Printed circuit board POW KHS095A for KHS0951 Top view Bottom view ...
Page 42: ...38 6 Printed circuit board POW KHS125A for KHS1251 Top view Bottom view ...
Page 43: ...39 7 Printed circuit board POW KHS095B for KHS0951 and KHS1251 Top view Bottom view ...
Page 44: ...40 8 Printed circuit board POW KHS1852 for KHS1852 Top view Bottom view ...
Page 45: ...41 9 Printed circuit board POW CH095 for CH0951 CH1251 and CH1852 Top view ...
Page 72: ...68 INSTRUCTION MANUAL KHS0951 CH0951 KHS1251 CH1251 KHS1852 CH1852 APPENDIX ...