8-6. Cold draft Prevention (Heating)
●
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat
exchange coil have sufficiently warmed up.
●
STANDBY lamp on front of the indoor unit lights up when this function is working.
●
when 10 minutes has elapsed,the fan speed is automatically switched to set speed regardless of indoor heat
exchange coil temperature.
OFF
ON
LL
OFF
Set speed
Indoor fan
Standby lamp
Indoor heat exch.
coil temp. (
¡
F)
95
77
Max. 10minutes