I - 112
SM830063
ECO MULTI SYSTEM Unit Specifications
1
9. Floor-Standing Type (F Type)
Unit specifications (C)
MODEL No.
Indoor Unit
SPW-FR183GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
5.6
6.3
BTU / h
19,000
21,000
Air circulation (Hi / Me / Lo)
m
3
/ h
900 / 780 / 660
Moisture removal (High)
Liters / h
2.5
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
*
A
0.54 -
0.56 -
0.58
0.37 -
0.41 - 0.43
Power input
W
116 -
126 -
136
79 -
91 -
101
Power factor
%
97.6 -
97.8 -
97.7
97.1 -
96.5 - 97.9
Max. starting amperes
A
1 - 1 - 1
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max.72 hr)
Fan speeds
3 and Automatic control
Air filter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound
(Hi / Me / Lo)
dB-A
39 / 36 / 31
Refrigerant tubing connections
Flare type
Refrigerant tube
Narrow tube mm (in)
9.52 (3 / 8)
outer diameter
Wide tube
mm (in)
15.88 (5 / 8)
Drain connection
20A, OD26mm
Drain pump
–
Drain pump (drain connection)
Optional (RCS-SH80TG)
Remote controller (option)
Optional / drain hose
Color (Approximate value)
Munsell 10Y9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Dimensions
Height
mm (in)
615 ( 24 - 7 /32)
694 (27 -
-
10/32 )
Width
mm (in)
1380 ( 54 - 11 /32)
1472 (57 -
-
30/32 )
Depth
mm (in)
230 ( 9 - 2 /32)
312 ( 12 - 9 /32)
Net weight
kg (lb)
39 (
86
)
Shipping weight
kg (lb)
41 (
90
)
Shipping volume
m
3
(cu. ft)
0.319 (
11.3
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling :
Rating conditions(
*
) :
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating :
Rating conditions(
*
) :
Indoor air temperature 20
°
C DB, Outdoor air temperature 7
°
C DB / 6
°