ECO MULTI SYSTEM Unit Specifications
SM830063
I - 13
1
1. Outdoor Unit
Outdoor Unit (C)
MODEL No.
SPW – CR703GVH8 / SPW – CR703GV8
Source
380 - 400 - 415 V / 3 phase / 50Hz
Controller P.C.B. Ass’y
CR - CR703GVH / CR - CR703GV
Control circuit fuse
250 V , 3.15 A
Compressor
Rotary (Hermetic)
PC (Power Control)
AC (Standard)
Model … Code No.
C-5RN373H8R ... 80838788
C-5RN373H8C ... 80838588
Nominal output
kW
3.75
3.75
Compressor oil (ETHER FV68S)
cc
2,000
2,000
Coil resistance
Ω
V - U: 2.83
, U - W: 2.65
V - U: 2.83
, U - W: 2.65
(Ambient temperature 25
°
C)
W - V: 2.78
W - V: 2.78
Safety devices
Thermal protector ON / OFF
°
C
120
±
5 / 98
±
11
120
±
5 / 98
±
11
Microprocessor safety devices
Compressor current detection circuit
Compressor discharge gas temperature control
Defective and negative phase detection circuit
Voltage drop detection circuit
Crank case heater
V, W
240 , 32
240 , 32
Fusible plug (Operating temp.)
°
C
73
±
2
High pressure switch
ACB - 1TB14W (T
U
V Approved)
Set pressure
ON / OFF
kg/cm
2
23.5
±
2.0 / 31.4
+ 0
Fan (Number … diameter(mm))
Propeller (1 … ø 750)
Fan motor
Model … Nominal output
W
KFJ8T - 301B3P … 300 W
No. of pole … r.p.m. (230 V, High)
8 … 576 r.p.m.
Coil resistance
Ω
BRN - WHT
: 11.89
WHT -
VLT
: 4.156
VLT
-
YEL
: 9.639
(Ambient temperature 20
°
C)
WHT - PNK
: 12.51
Safety device
Thermal protector ON / OFF
°
C
(115
±
5) / 130
±
5
Run capacitor
VAC ,
µ
F
400 V , 15.0
µ
F
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows … fin pitch
mm
2 … 1.7
Face area
m
2
2.40
– 1. 5