ECO MULTI SYSTEM Unit Spesifications
SM830063
I - 8
1
1. Outdoor Unit
Unit specifications (F)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19.0
°
C WB
, Outdoor air temperature 35
°
C DB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32
°
C DB / 22.5
°
C WB , Outdoor air temperature 43
°
C DB / 25.5
°
C WB
MODEL No.
Outdoor Unit
SPW – CR703GV8
POWER SOURCE
380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE
Cooling
Capacity
kW
22.4
BTU / h
76,400
Air circulation (Hi)
m
3
/min(cu. ft/min)
155 (5,470)
ELECTRICAL RATINGS
Voltage rating
V
380 - 400 - 415
Available voltage range
V
342 - 456
Running
amperes
A
15.8 - 15.2 -
14.9
Max. running amperes*
A
20.6 - 19.6 -
19.2
Power
input
kW
9.45 - 9.50 -
9.56
Max. power input*
kW
12.1 - 12.2 -
12.4
Power
factor
%
90.9 - 90.2 -
89.3
C.O.P
W/W
2.37 - 2.36
-
2.34
Compressor locked rotor amperes
A
51 -
53 -
55
FEATURES
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment
kg
R407C - 9.5
Refrigerant control
Electronic expansion valve
Operation sound (Hi)
dB-A
58
Compressor
Super power control twin rotary compressor
Color (Approximate value)
Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length
m(ft.)
100 (328)
Limit of elevation difference
m(ft.)
Outdoor unit is higher than indoor unit : 50 (165)
between the two units
Outdoor unit is lower than indoor unit : 30 (100)
Refrigerant tube
Narrow tube mm (in)
12.7 ( 1/ 2 )
outer diameter
Wide tube
mm (in)
25.4 (
1
)
Refrigerant tubing kit / joint kit
Optional
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm(in)
1,218 (48
)
1,351 (53 - 1 / 4)
Width
mm(in)
883 (34 - 3 / 4)
1,047 (41 - 1 / 4)
Depth
mm(in)
883 (34 - 3 / 4)
1,005 (39 - 5 / 8)
Net weight
kg(lb)
229 (
505
)
Shipping weight
kg(lb)
229 (
505
)
Shipping volume
m
3
(Cu. ft.)
1.42 (
50.1 )