SM830063
I - 67
1
ECO MULTI SYSTEM Unit Specifications
5. Wall Mounted Type
5-5. Noise criterion curves
MODEL
: SPW-KR93GH56
SOUND LEVEL
: HIGH
38 dB(A),
NC 33
LOW
30 dB(A),
NC 25
CONDITION
: Distance 1 m,
Under the unit 1 m
SOURCE
: 220 - 230 - 240 V, 1 Phase, 50 Hz
MODEL
: SPW-KR123GH56
SOUND LEVEL
: HIGH
40 dB(A),
NC 35
LOW
34 dB(A),
NC 29
CONDITION
: Distance 1 m,
Under the unit 1 m
SOURCE
: 220 - 230 - 240 V, 1 Phase, 50 Hz
0291_K_I
90
80
70
60
50
40
30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB
(0 dB = 0.0002 µbar)
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0290_K_I
90
80
70
60
50
40
30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB
(0 dB = 0.0002 µbar)
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MODEL
: SPW-KR183GH56
SOUND LEVEL
: HIGH
46 dB(A),
NC 41
LOW
37 dB(A),
NC 32
CONDITION
: Distance 1 m,
Under the unit 1 m
SOURCE
: 220 - 230 - 240 V, 1 Phase, 50 Hz
REMARKS: 1. Value obtained in the actual place
where the unit is installed may be
slightly higher than the values shown in
this graph because of the conditions of
operation, the structure of the building,
the background noise and other factors.
2. The test results were obtained from an
anechoic room.
NOTE To evaluate “Noise level” the maximum number
of the measured OCTAVE BAND SOUND
PRESSURE LEVEL is used. Read the number
on each BAND CENTER FREQUENCIES
(horizontal axis) ranging from 63 Hz to 8000 Hz
and select the maximum value (vertical axis)
among them.
0292_K_I
90
80
70
60
50
40
30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB
(0 dB = 0.0002 µbar)
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20