P a g e
|
30
Optidrive E3 Set-up Guide
9
Keypad Control
P-15 = 3
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
3
Open: Stop (disable)
Closed: Run (enable)
Open: No function
Closed: Increase speed
External trip input
Open: Trip
Closed: Run (No trip)
Open: No function
Closed: Decrease speed
NOTE:
For motor thermistor, connect PTC between 24V and digital input 3 (Terminals 1 and 4) and set
parameter P-47 =
PTc~Th
NOTE:
Analogue input 1 used as a digital input.
P-15 = 4
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
4
Open: Stop (disable)
Closed: Run (enable)
Open: No function
Closed: Increase speed
Open: Keypad speed ref
Closed: Analogue input 1
Analogue input 1
P-15 = 5
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
5
Open: Stop (disable)
Closed: Run (enable)
Open: Forward
Closed: Reverse
Open: Keypad speed ref
Closed: Analogue input 1
Analogue input 1
P-15 = 6
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
6
Open: Stop (disable)
Closed: Run (enable)
Open: Forward
Closed: Reverse
External trip input
Open: Trip
Closed: Run (No trip)
Open: Keypad speed ref
Closed: Preset speed 1 (P-20)
NOTE:
For motor thermistor, connect PTC between 24V and digital input 3 (Terminals 1 and 4) and set
parameter P-47 =
PTc~Th
NOTE:
Analogue input 1 used as a digital input.
P-15 = 7
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
7
Open: Stop (disable)
Closed: Run Forward
Open: Stop (disable)
Closed: Run Reverse
External trip input
Open: Trip
Closed: Run (No trip)
Open: Keypad speed ref
Closed: Preset speed 1 (P-20)
NOTE:
For motor thermistor, connect PTC between 24V and digital input 3 (Terminals 1 and 4) and set
parameter P-47 =
PTc~Th
NOTE:
Analogue input 1 used as a digital input.
NOTE:
Closing digital inputs 1 and 2 (terminals 2 and 3) together carried out a Fast Stop (parameter P-24)