Optidrive E3 Set-up Guide
P a g e
|
27
8
Control Terminal Functionality
P-15 = 15
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
15
Open: Stop (disable)
Closed: Run (enable)
Open: Preset speed 4 (P23)
Closed: Analogue input 1
Fire mode activation
(Logic set in P-30)
Analogue input 1
P-15 = 16
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
16
Open: Stop (disable)
Closed: Run (enable)
Open: Preset speed 4 (P-23)
Closed: Preset speed 2 (P-21)
Fire mode activation
(Logic set in P-30)
Open: Forward
Closed: Reverse
NOTE:
Analogue input 1 used as a digital input.
P-15 = 17
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
Preset speed selected
17
Open: Stop (disable)
Closed: Run (enable)
Open
Fire mode activation
(Logic set in P-30)
Open
Preset speed 1 (P-20)
Closed
Open
Preset speed 2 (P-21)
Open
Closed
Preset speed 3 (P-22)
Closed
Closed
Preset speed 4 (P-23)
NOTE:
Analogue input 1 used as a digital input.
NOTE:
4 preset speeds selectable using digital input 2 and analogue input 1 (terminals 3 and 6).
P-15 = 18
P-15
Digital input 1
Terminal 2
Digital input 2
Terminal 3
Digital input 3
Terminal 4
Analogue input 1
Terminal 6
18
Open: Stop (disable)
Closed: Run (enable)
Open: Forward
Closed: Reverse
Fire mode activation
(Logic set in P-30)
Analogue input 1
NOTES
- Negative preset speeds will be inverted if Run Reverse is selected.
- When a motor thermistor is set up, the drive will trip on
F~PTc
if the thermistor resistance exceeds 3kΩ. The
trip cannot be reset until the resistance falls below 1kΩ.
Connection diagrams for P-15
NOTE:
These connection diagrams only show the connections for Digital inputs 1, 2 & 3 and analogue input 1
(Terminals 2, 3, 4 and 6).