60
Input registers (Read)
Register Discrete input
Data type Range
Default Comments
3000
1
SetPoint
16bits
0-100
-
P1 potentiometer position (%)
3000
2
SetPoint Value
16bits
0-2000
-
P1 potentiometer value (ppm
or HR)
3000
3
Light guide
intensity
16bits
0-100
-
P2 potentiometer position (%)
3000
4
Analog Output
16bits
0-100
-
Analogue output (Vdc)
(Example: 56 = 5,6Vdc)
3000
5
IAQ sensor TVOC
16bits
125-600
-
VOC sensor equivalent value
(ppb)
3000
6
IAQ sensor CO2
16bits
450-2000
-
VOC sensor equivalent value
(ppm)
3000
7
Temp sensor
16bits
-100-500
-
Temperature sensor value (°C)
(Example: 213 = 21,3°C)
3000
8
Hum sensor
16bits
0-100
-
Humidity sensor value (%HR)
3000
9
CO2 sensor
16bits
450-2000
-
CO2 sensor value (ppm)
300
10
Working mode
16bits
1 : MF1
2 : MF2
3 : MF3
4 : MF4
-
Operating mode
300
11
Version
Unsigned
16bits
1 : RH
2 : VOC
3 : CO2
-
Airsens version