16
EN
MF3: 2 -10Vdc output
+ Modbus (reading)
Adjustable
α
angle via
P1 potentiometer
ɲ
Input
Output
10V
2V
450ppm
45%HR
2000ppm
100%HR
800ppm
60%HR
MF4: Modbus control
Access to all operating modes and parameters via Modbus
communications (see Fig.3).
Note: If other switch combination is chosen, LED diffuser is switched off and digital/
analogue signals are inoperative.
P1 potentiometer
position
(%)
MF1 mode: Set Point
MF2/MF3 mode: Upper limit
ppm
HR
0
800
60
5
860
62
10
920
64
15
980
66
20
1040
68
25
1100
70
30
1160
72
35
1220
74
40
1280
76
45
1340
78
50
1400
80
55
1460
82
60
1520
84
65
1580
86
70
1640
88
75
1700
90
80
1760
92
85
1820
94
90
1880
96
95
1940
98
100
2000
100