![background image](http://html2.mh-extra.com/html/sandc/vacufuse/vacufuse_installation-and-operation-manual_3076732022.webp)
22 S&C Instruction Sheet 465-500
Troubleshooting
be attached so it reaches across the front of the
VacuFuse Self-Resetting Interrupter and the
Loadbuster tool’s anchor must be hooked to the
attachment hook on the far side of the VacuFuse
interrupter.
The Loadbuster tool should never be attached
with its anchor hooked on the closest side of the
VacuFuse interrupter, as shown in Figures 25
and 26. Attaching the tool in this manner will
not only obscure the operator’s line of vision,
but it could also result in bending stress on the
tool, causing improper disengagement.
Figure 25. An incorrect fastening approach.
Figure 26. An incorrect fastening approach.