24 S&C Instruction Sheet 465-500
Troubleshooting
To perform this operation smoothly, always
roll the Loadbuster tool so that it rotates in an
upward direction.
STEP 7.
To reset the Loadbuster tool for the next
operation, hold it as shown in Figure 28. Extend
the tool slightly and lift the resetting latch with
your thumb. With the latch up, telescope the tool
completely so the trigger can reset itself.
Depress the telescoping tube until the orange
paint on the inner tube assembly is no longer
visible.
Check for proper resetting by extending the
tool about 3 inches (76 mm). Throughout this
travel, an increasing spring resistance should
be felt.
Note:
When the VacuFuse Self-Resetting Interrupter is
opened with a Loadbuster tool, the vacuum interrupter
inside the VacuFuse interrupter will not be triggered open
and will remain closed.
Resetting latch
Figure 28. Resetting a Loadbuster tool.