Installation
on
S&C Mounting Pedestals
Wiring the Pole-Unit Connections
For optional quick-connect control cable skip
to Step 44.
Step 42
Remove the three removable screws at each
pole-unit electrical junction box cover. Retain
the screws. Loosen the fourth retaining screw.
Then swing out the cover to access the wiring
inside the electrical junction box. See Figures
42 and 43.
Ç
WARNING
DO NOT remove the window bolts .
The pole-unit is pressurized to 75 psig .
Serious injury could occur.
Step 43
Following the wiring diagram furnished, con-
nect the conduit wiring to the wiring inside the
electrical junction boxes. Use the butt splices
attached to the junction-box wiring. The butt
splices accommodate 18 to 22 AWG wire. Use
of 18-gauge wiring is recommended.
NOTICE
To ensure proper crimping of the butt splices,
use the Panduit controlled-cycle hand tool
(CT-1550), or equivalent for attaching 18- to
20-gauge insulated ring lugs .
Figure 43. Swing out the cover to access the wiring inside the electrical
junction box.
Underside of pole-
unit junction box
Electrical
junction box
Cover
Figure 42. Remove the three removable screws at each pole-unit electrical
junction box cover. Loosen the fourth retaining screw.
Retaining screw
Cover
Removable screws
Underside of
pole-unit base
Window bolts—
DO NOT REMOVE
Figure 44. Securely tighten the screws of the electrical junction box
covers.
Retaining screw
Cover
Removable screws
Underside of
pole-unit base
Step 44
Rotate the cover of each electrical junction
box and replace the retained screws. Securely
tighten all screws. See Figure 44.
24
S&C Instruction Sheet 731-502