627-500 28
Step 33
Install and connect surge arresters, if applicable.
Step 34
Sweep debris from the fl oors of the modules and wipe
barriers, insulators, bushings, terminators, switches,
and fuses clean with a mineral-spirits solvent. Dry with
a clean dry cloth.
Step 35
Check functional operation of key and mechanical
interlocks, if furnished.
Step 36
Remove all shipping tapes and “module-number” labels
and clean up any remaining adhesives. Wipe down the
exterior of the modules with a clean damp cloth.
Ç
CAUTION
Before Walking Away . . .
1. Check the interior of each module for foreign
materials, tools, etc., that may have been mislaid
on high-voltage bus and supporting members.
2. Make certain that switch operators, if furnished,
are coupled to interrupter switches.
3. Make certain that all selector switches on the
source-transfer control—if applicable—are in
the desired position.
4. Make certain that all fuses are fully closed and
latched.
5. Close and securely latch all switchgear module
doors.
6 Make certain that all interrupter switches are in
the correct positions, open or closed, as dictated
by electrical system design.
7. Make certain that all grounding means have been
removed.
8. Padlock all doors, handles, switch-operating
handles, and covers (if applicable).
Additional instructions on correct positioning
of specifi c components are contained in the S&C
instruction sheets for those components. Refer to the
instruction manual provided with the switchgear.