Appendix
Step C
Highlight and select
Change
. The default configuration data window will appear, as
shown below.
Step D
Select the default values of all “Not Changeable” items. Refer to Quick-Start Programming
Instruction Sheet 515-530 or Instruction Sheet 515-500 or 515-600 for details.
NOTICE
Each default value you select must conform with the corresponding factory-set item
in your Micro-AT con trol(s). When you subsequently download the configu ration file
you’re creating to a particular Micro-AT control, Matlink will compare each default
value to the corresponding factory-set item in the CONFIGURE menu of the control.
If there are any conflicts, the downloaded configuration will not be accepted.
For instance, if the CONFIGURE menu of the con trol is presently factory-set for
a common-bus metal-enclosed switchgear application, then a configuration for a
pad-mounted gear application cannot be entered into the control.