Programming

NOTICE

This section provides a summary of basic programming requirements . 
Programming should not be started until site and system requirements 
have been established and S&C Instruction Sheet 1045-530, “6800 
Series Automatic Switch Controls with IntelliTeam® SG Automatic 

 

Restoration System: 

Setup

” has been thoroughly reviewed .

When you have a screen question, press the <F1> key to open the help section for the 
screen being viewed. This is a very handy IntelliLink software resource.

Many settings will be the same for most controls in a system. Making a setting template 
with the common settings saves time and reduces setting errors. Because of this, most 
users configure a control in the office, save a setpoint file with the unique site values, 
and simply load that file into the control in the field.

After configuring the control: 

follow these steps to save a setpoint file:

STEP  1.  

Click on the 

File

 drop-down menu and click on the Save Setpoints entry.

STEP  2.  

Enter the file name and location in the 

Save as

 field.

STEP  3.  

In the Save Setpoint Profile dialog box, choose the setpoint values to be saved.

(a)  To save the stand-alone setpoint values, make sure the General and 

Communication check boxes are checked and the Restoration check box is 
unchecked. Then, click on the 

Save

 button.

(b)  To save the team setpoint values, click on the 

Profile: Team x Setpoints

 

option for the desired team. Then, click the 

OK

 button.

(c)  To save all setpoint values, including values for teams that may not have 

been configured, click on the 

Select All

 option. Then, click on the 

OK

 

button.

At the site: 

follow these steps to load a setpoint file into the control:

STEP  1.  

Click on the 

File

 drop-down menu and click on the Load Setpoints entry.

STEP  2.  

Select the CFG file to be loaded and click on the 

Open

 button.

STEP  3.  

Specific setpoint changes required for this control can now be entered. For 
stand-alone setpoints, enter the correct value for the 

Physical Location 

setting, the 

Local Device DNP Address

 setting, and the sensor configuration 

data, if applicable.

STEP  4.  

If the CFG file contains security settings and the Security check box is  
selected, the authentication/login credentials will be reset to those in the CFG 
file. Have a clear understandinf of what those are before loading them.

NOTICE

Controls with lost passwords must be returned to the factory to be reset to the 
default values .

Setpoint Files

S&C Instruction Sheet 1045-511    15

Summary of Contents for 6800 Series

Page 1: ...tch Control Configuration Log In to the Control 8 Software Screen Features 9 Validate Apply Screen 9 Security 10 General Setup 11 Sensor Configuration 12 Site Related Settings 13 Metering 13 Saving a Memory Snapshot 14 Communications 14 Programming Setpoint Files 15 IntelliTeam System Configuration 16 Stand Alone Programming 16 Automatic Operation 16 SCADA Point Mapping 17 January 6 2020 S C Elect...

Page 2: ...nent part of your 6800 Series Automatic Switch Control Designate a location where you can easily retrieve and refer to this publication The standard warranty contained in S C s standard conditions of sale as set forth in Price Sheets 150 and 181 applies to the 6800 Series Automatic Switch Control except that the first paragraph of the said warranty is replaced by the following 1 General The seller...

Page 3: ...ty of the 6800 Series Automatic Switch Control is contingent upon the installation configuration and use of the control or software in accordance with S C s applicable instruction sheets This warranty does not apply to major components not manufactured by S C such as batteries and communication devices However S C will assign to the immediate purchaser or end user all manufacturer s warranties tha...

Page 4: ...autions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance contact the nearest S C Sales Office or S C Authorized Distributor Their telephone numbers are listed on S C s website sa...

Page 5: ...s Automatic Switch Control must be restricted only to qualified persons See the Qualified Persons section on page 2 2 SAFETY PROCEDURES Always follow safe operating procedures and rules 3 PERSONAL PROTECTIVE EQUIPMENT Always use suitable protective equipment such as rubber gloves rubber mats hard hats safety glasses and flash clothing in accordance with safe operating procedures and rules 4 SAFETY...

Page 6: ...hes in Remote Supervisory PME and PMH Pad Mounted Gear Remote Supervisory Vista and Vista SD Underground Distribution Switchgear and a variety of switches from other manufacturers 6800 controls can be operated in two states Local and Remote When set to the Remote state SCADA commands are permitted When set to the Local state SCADA commands are blocked and the 6800 control can be operated by the fa...

Page 7: ...trol faceplate Figure 2 The 6801 control Operation screen Automatic Restoration mode SCADA Control mode Automatic Operation mode Automatic Restoration mode SCADA Control mode Automatic Operation mode S C Instruction Sheet 1045 511 7 ...

Page 8: ...045 510 and 1045 540 have more information about the battery STEP 4 When the control is powered connect the computer to the control by a cable to one of the DATA PORTS on the faceplate Use a USB A to B cable or a serial cable Wi Fi can be used to connect to a control that has the Wi Fi option STEP 5 On the computer double click on the IntelliLink icon to launch the software STEP 6 Click on the Loc...

Page 9: ... configuration changes are validated and applied See Figure 5 on page 10 The Validate button evaluates settings in the buffer memory without applying them When changes are pending click on the Validate button to initiate a logical check of the pending changes for errors If the procedure detects an error or inconsistency it will be displayed in the Validation Result field The Apply button evaluates...

Page 10: ...s an Admin can make changes to this screen The User Group name can be changed for all groups except Admin and Viewer All passwords can be changed Passwords have no restrictions on characters and the max character limit is 12 A dialog box will open when the value to change is clicked on Changes do not take effect until the Apply button is clicked on in the Setup Validate Apply screen Security Figur...

Page 11: ...ral screen See Figure 7 The SG6800 tab configures name and location information for the switch control Name this control in the Device Name field and enter the location in the Device Location field These fields display to identify this control when you log in General Setup Figure 7 The Setup General SG6800 screen S C Instruction Sheet 1045 511 11 ...

Page 12: ...tion also stamped on each sensor Enter the information on this screen The 6801 controls do not have this card but the information is part of the data package provided with the Scada Mate switch Because the controls and switches are typically shipped separately it is important to make sure the information stays with the switch until it is pared with a control Sensor Configuration Figure 8 The Setup...

Page 13: ...omer voltage reporting The control uses this information when calculating kvars Set as either Phase to Neutral or Phase to Phase mode At the bottom of the screen are the Installation Voltage Current Phase Angle Offset settings The setpoints one for each voltage current phase allow installation dependent phase angle corrections The angle offsets are used to determine the Normal Current and Reverse ...

Page 14: ... name and location to save this snapshot STEP 3 Click on the Save button Saving a Memory Snapshot Remote com mu n icat ion ca n be con f ig u red for t he I ntel l iTea m SG Automatic Restoration System SCADA communications and IntelliLink Setup Software See Figure 11 Information supplied by the department that supports your field area net work is entered on this screen All the settings are define...

Page 15: ...a To save the stand alone setpoint values make sure the General and Communication check boxes are checked and the Restoration check box is unchecked Then click on the Save button b To save the team setpoint values click on the Profile Team x Setpoints option for the desired team Then click the OK button c To save all setpoint values including values for teams that may not have been configured clic...

Page 16: ...ground faults The setpoint values are on the Setup General Fault Detection screen These settings define the fault Currents on all three phases are monitored and compared with these setpoints Stand Alone Programming The Automatic Operation tab configures various automatic switch control operations See Figure 12 For the 6802 and 6803 Automatic Switch Controls configure most setpoints as separate val...

Page 17: ...x position of the selected point defining the order in which the points are returned to SCADA For a detailed description of the DNP point in your control refer to the appropriate S C instruction sheet on sandc com The DNP Points List instruction sheets have the prefix 1045 560 SCADA Point Mapping Figure 13 The Setup Point Mapping Status screen S C Instruction Sheet 1045 511 17 ...