INSTALLATION
Argus Installation and Resource Guide
15
2.5
WIRING RELAYS
Wiring relays involves connecting two wires to the zone card terminal block. Connect
terminal 5 to A1 and connect terminal 6 to A2, according to the figure below.
Figure: Alarm relay wiring
•
Consult your electrician about tying the relay to equipment that needs to shut
down automatically.
•
If a relay needs to be replaced, Samuel Jackson supplies a triple pole double
throw 24V DC relay that is rated to 10 amps.
Note
: The resistor between 11 and 12 should be left in place.
84020 REV A
Argus XTRA Multizone Manual
page: 12
D.C. Power
Zone Power
Detector
Trouble
Zone Reset
switch
Relay/Extinguisher
Disconnect switch
Terminal block
Terminal block
Extinguisher
Card static Maximum Power Consumption:
30mA Regulated
1mA Unregulated
Maximum Detector Per Control Panel:
Z-10 - 60 Argus 343 Detectors
Z-20 - 120 Argus 343 Detectors
Maximum Detectors Per Zone:
Argus 343 Detectors - 16
2 AMPs
(fUsED)
EXT
field Wiring
AnUC
PWR
ARGUs ZonE CARD
front
Right side
AlM
Reset
2 AMP
DET
REl
AUX
EXT
black
1
1
In
nC
nC
s
H
lD
2 3 4
5 6 7
8
9
10 11 12
12
1
1
1
1
Detector Circuit
End of
line
Module
2
2
2
2
3
3
3
3
+
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
-
-
AnUC
AnUC
AnUC
AnUC
oUT
oUT
oUT
oUT
White
Red
Green
Ground
Ground
Ground
Ground
REl/EXT DIsC
Extinguisher
Trouble
figure 8.2
Zone Card
A2
A1
Summary of Contents for Argus
Page 1: ...Installation and Resource Guide...
Page 2: ......
Page 29: ...SUPPLEMENTAL Argus Installation and Resource Guide 27...
Page 30: ...SUPPLEMENTAL Argus Installation and Resource Guide 28...
Page 31: ...SUPPLEMENTAL Argus Installation and Resource Guide 29...
Page 37: ...SUPPLEMENTAL Argus Installation and Resource Guide 35...
Page 38: ...WARRANTY Argus Installation and Resource Guide 36...
Page 40: ...Argus Installation and Resource Guide 38 This page left intentionally blank...