INSTALLATION
Argus Installation and Resource Guide
17
2.7
TESTING FOR GROUND FAULT
After all detectors have been wired into the control panel and you are performing a final
check of the panel, use this procedure for a ground fault test:
•
Monitor Card with Ground Fault Indicator Test Switch:
o
Disconnect chassis ground from Terminal #4 on the power card.
o
Push the Ground Fault Indicator (GFI) Test Switch on the Alarm Monitor Card.
o
Release the Test Switch and re-connect chassis ground to Terminal #4 on the
Power Card.
•
Monitor Card without Ground Fault Indicator Test Switch:
o
Disconnect chassis ground from Terminal #4 on Power Card.
o
Connect a jumper between Terminal #1 and Terminal #2 on the Alarm Monitor
Card.
o
Disconnect the jumper between Terminal #1 and Terminal #2 on Alarm Monitor
Card.
o
Reconnect the chassis ground to Terminal #4 on the Power Card.
NOTE: If there is a ground in the system, the amber Ground Fault Indicator LED (GDF)
will light on the Alarm Monitor Card. There will be no beeper sound.
If there is not a ground in the system, because there is no trouble signal the amber Ground
Fault Indicator LED (GDF) on the Alarm Monitor Card will not light.
Summary of Contents for Argus
Page 1: ...Installation and Resource Guide...
Page 2: ......
Page 29: ...SUPPLEMENTAL Argus Installation and Resource Guide 27...
Page 30: ...SUPPLEMENTAL Argus Installation and Resource Guide 28...
Page 31: ...SUPPLEMENTAL Argus Installation and Resource Guide 29...
Page 37: ...SUPPLEMENTAL Argus Installation and Resource Guide 35...
Page 38: ...WARRANTY Argus Installation and Resource Guide 36...
Page 40: ...Argus Installation and Resource Guide 38 This page left intentionally blank...