50_
I/O time setup
I/O time setup
READER #1 ERROR OUTPUT SETUP
READER #1 ID Error Output Setup
Press the
F
6
SETUP MENU button.
Use the buttons
4
and
6
to move to the
RD1 ID ERROR
item and
press
ENT
.
You can make input when the prompt blinks.
If you enter ‘00’, no output setting is configured.
Use the keypad to enter the time for each output operation and press
ENT
.
DR : Door relay output
AR : Alarm relay output
T1 : TTL #1 output
T2 : TTL #2 output
BZ : Buzzer output
The output time differs, depending on the time unit.
If the time unit is 0.1 (second), you can specify the value between 0.0 and 9.8 second; if set to 1 (second), you can
specify between 0 and 98 seconds.
For the time unit, refer to the ‘Time Unit Setup’ under the advanced setup. (see page 54)
If you enter 99 for the value, the product stays in output mode until you change the setting regardless of the time
unit.
READER #1 Time Schedule Error Output Setup
Press the
F
6
SETUP MENU button.
Use the buttons
4
and
6
to move to the
RD1 T/S ERROR
item and
press
ENT
.
The operation time for each output is the same as in “READER #1 ID Error
Output Setup” above.
Time schedule must be confi gured before. (See Page 55 for “Time Schedule Setup”.)
READER #1 Antipassback Error Output Setup
Press the
F
6
SETUP MENU button.
Use the buttons
4
and
6
to move to the
RD1 APB ERROR
item and
press
ENT
.
The operation time for each output is the same as in “READER #1 ID Error
Output Setup” above.
APB mode must be enabled before. (See Page 55 for “AntiPassBack Mode”.)
1.
2.
3.
•
•
M
1.
2.
•
M
1.
2.
•
M
5.RD1 ID ERROR
D R A R T 1 T 2 B Z
0 0 0 3 0 0 0 0 0 0
5.RD1 ID ERROR
D R A R T 1 T 2 B Z
_ 0 0 3 0 0 0 0 0 0
7.RD1 APB ERROR
D R A R T 1 T 2 B Z
0 0 0 3 0 0 0 0 0 0
6.RD1 T/S ERROR
D R A R T 1 T 2 B Z
0 0 0 3 0 0 0 0 0 0