Installation
Out
door Units
NOTE
• RLA is based on AHRI 210/240 cooling standard
condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 °C /
67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)]
•
Voltage tolerance is ± 10 %.
•
Maxi
m
um allowable voltage between phases is 2 %.
•
Symbols
– RLA: Rated Load Ampere (A)
– MOC: Maximum Operating Current (A)
– MCA: Min
i
mum Circuit Ampere (A)
– MOP: Maximum Overcurrent Protective Device (A)
• Voltage range
– Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
• Maximum allowable voltage variation between phases
is 2%.
• Wire size & type must comply with the applicable local
and national code.
– Wire size: Based on the value of MCA.
– Wire type:
1-
phase: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more
Silence mode controller wiring diagram with
External controller
•
AC009/012/018BXADCH
2Pin
(RED)
4Pin
(RED)
Non-voltage contact
External controller
•
AC024/030/036/042/048BXADCH
2Pin (RED)
4Pin(RED)
Non-voltage
contact
External controller