6. Capacity Correction
CNH18
L
DB(AC018BN
L
DCH/AA)+CXH18ADB(AC018BXADCH/AA)
CNH18HDB(AC018BNHDCH/AA)+CXH18ADB(AC018BXADCH/AA)
CNH24
H
DB(AC024BN
H
DCH/AA)+CXH24ADB(AC024BXADCH/AA)
CNH30
H
DB(AC030BN
H
DCH/AA)+CXH30ADB(AC030BXADCH/AA)
Cooling
Pipe Length (ft)
24.6
32.8
49.2
65.6
82.0
98.4
114.8
131.2
147.6
164.0
Le
vel Diff
er
enc
e (ft
)
98.4
-
-
-
-
-
0.94
0.93
0.92
0.91
0.90
82.0
-
-
-
-
0.96
0.94
0.93
0.92
0.91
0.90
65.6
-
-
-
0.97
0.96
0.94
0.93
0.92
0.91
0.90
49.2
-
-
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
32.8
-
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
16.4
1.00
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
0.0
1.00
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-16.4
1.00
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.90
0.88
-32.8
-
0.98
0.97
0.96
0.95
0.94
0.92
0.91
0.89
0.87
-49.2
-
-
0.97
0.96
0.94
0.93
0.92
0.90
0.88
0.85
-65.6
-
-
-
0.95
0.94
0.93
0.91
0.89
0.87
0.83
-82.0
-
-
-
-
0.94
0.92
0.91
0.89
0.86
0.82
-98.4
-
-
-
-
-
0.92
0.90
0.88
0.85
0.80
Heating
Pipe Length (ft)
24.6
32.8
49.2
65.6
82.0
98.4
114.8
131.2
147.6
164.0
Le
vel Diff
er
enc
e (ft
)
98.4
-
-
-
-
-
0.94
0.93
0.92
0.91
0.90
82.0
-
-
-
-
0.96
0.94
0.93
0.92
0.91
0.90
65.6
-
-
-
0.97
0.96
0.94
0.93
0.92
0.91
0.90
49.2
-
-
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
32.8
-
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
16.4
1.00
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
0.0
1.00
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-16.4
1.00
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-32.8
-
0.99
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-49.2
-
-
0.98
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-65.6
-
-
-
0.97
0.96
0.94
0.93
0.92
0.91
0.90
-82.0
-
-
-
-
0.96
0.94
0.93
0.92
0.91
0.90
-98.4
-
-
-
-
-
0.94
0.93
0.92
0.91
0.90
Outdoor Units