3. Capacity Table
(
6
)
CNH36
H
DB(AC036BN
H
DCH/AA) + CXH36ADB (AC036BXADCH/AA)
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Heating
TC : Total Capacity, PI : Power Input
NOTE
•
The performance table shows the average value of each conditions.
Duct S
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
0
36.6 26.4 3.16 38.6 27.3 3.23 40.2 28.1 3.29 41.4 29.0 3.36 42.2 28.7 3.39 44.3 28.4 3.43 46.6 27.8 3.50
70
38.2 27.6 2.85 40.2 28.5 2.90 41.9 29.3 2.96 43.2 30.2 3.02 44.1 29.9 3.05 46.3 29.6 3.08 48.6 29.0 3.15
95
31.8 23.0 3.16 33.5 23.7 3.23 34.9 24.4 3.29 36.0 25.2 3.36 36.7 24.9 3.39 38.6 24.7 3.43 40.5 24.2 3.50
115
28.7 23.7 3.79 30.2 24.4 3.87 31.4 25.1 3.95 32.4 25.9 4.03 33.0 25.7 4.07 34.7 25.4 4.11 36.4 24.9 4.19
122
23.9 20.9 2.85 25.1 21.6 2.90 26.2 22.3 2.96 27.0 23.0 3.02 27.5 22.7 3.05 28.9 22.5 3.08 30.4 22.0 3.15
Outdoor
Temp.
(℉, DB)
Indoor Temperature (℉, DB / WB)
68 / 57
72 / 61
77 / 64
80 / 67
82 / 70
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
-4
34.0
5.10
33.7
5.05
33.3
5.00
33.0
4.95
32.7
4.90
32.3
4.85
14
37.1
4.62
36.7
4.58
36.4
4.53
36.0
4.49
35.6
4.44
35.3
4.40
32
39.2
3.73
38.8
3.70
38.4
3.66
38.0
3.62
37.6
3.59
37.2
3.55
47
41.2
3.55
40.8
3.52
40.4
3.48
40.0
3.45
39.6
3.42
39.2
3.38
75.2
47.4
3.20
46.9
3.17
46.5
3.14
46.0
3.11
45.5
3.07
45.1
3.04
Outdoor
Temperature
(℉, DB)
Indoor Temperature (℉, DB)
61
64
68
70
22
24