PART 1. PRE-INSTALLATION INFORMATION
1.1 SITE REQUIREMENTS
Select a location that satisfies the following conditions for safety, temperature, humidity, power
and grounding.
1.1.1 Safety Conditions
The OfficeServ 7400 system should not be installed near materials that can cause a fire,
such as explosive gas and inflammables. The OfficeServ 7400 system should not be near
equipment that generates electromagnetic waves, such as monitors or copying machines.
The installation location should be convenient for distributing trunk lines and extension
lines, for connecting power and grounding wires, and for maintenance and repair.
The OfficeServ 7400 system should not be installed in aisles or passageways that are
populated or used for moving equipment.
Always maintain cleanliness to prevent dust from damaging the board connectors of the
cabinet.
Before installing the OfficeServ 7400 system, check items such as the electrical wiring
status, grounding status, voltage and frequency.
Do not expose equipment to direct sunlight, corrosive fumes, and constant vibrations.
Do not install in close proximity to a fire sprinkler or other sources of water.
A dedicated commercial AC power outlet is required. Do not use extension cords.
Ensure that all wires and cables to and from the OfficeServ 7400 do not cross fluorescent
lights or run in parallel with AC wires.
This equipment is to be installed only in restricted access areas (dedicated, equipment
closets, etc.) in accordance with articles 110-16, 110-17, 110-18 of the National Electric
Code, ANSI/NFPA 70.
1.1.2
Temperature/Humidity Conditions
The conditions for temperature and humidity are as follows:
Operation temperature: 32°F~113°F
Storage temperature: 14°F~122°F
Humidity: 10~90%