11
Item
Content
Remark
Schedule Period
Starting and ending date of a schedule
Exception Day
Setup
Set an exception day within a schedule period to
ignore the schedule control
Devices to
be applied
Select devices to receive schedule control
Event
Set indoor unit operation modes
- Device On time
- Device Off time
- Desired temperature
- Operation mode: Auto/Cool/Dry/Fan/Heat/Off
- Remote control usage Enable RC/ Disable RC/
Cond.RC
- Fan speed: Auto/Low/Mid/High
- Air flow: None/Vertical/Horizontal/All
- ERV operation mode: Auto/HeatEx/ByPass/Sleep
- ERV Fan speed: Low/High/Turbo
Weekly Repeat:
Maximum 10 events
per day
Daily Repeat:
Maximum 70 events
Main Function
The schedule function of the DMS2 can be set through the Web
or using the upper level controller. 1day/Everyday/Every week
schedules can be set.
Each schedule can be used selectively by using the run
schedule/stop schedule order.
At most 256 schedules can be set.
Indoor unit control is possible at least 1 minute of interval by
set schedule.
Set and Run Schedule