![Samsung MIM-B17 User Manual Download Page 36](http://html.mh-extra.com/html/samsung/mim-b17/mim-b17_user-manual_346095036.webp)
E-
36
4
Set cooling/heating discharge temperature by clicking [
] and [
].
When the MINI AHU is in Cool mode, you can adjust cooling discharge temperature
and when the MINI AHU is in Heat mode, you can adjust the heating discharge
temperature.
When the MINI AHU is in Auto, Dry or Fan mode, you cannot adjust the discharged
temperature.
Cooling discharged temperature can be set in the range of 8°C(47°F)~18°C(65°F).
Heating discharged temperature can be set in the range of 30°C(86°F)~43°C(110°F).
5
Select Humidification setting.
You can enable/disable button to decide whether to use ‘Humidification’ function.
Humidification function is only available in Heat mode.
6
Select desired humidity level.
You can select the humidity level from Low/Med/High.
Humidity level can be adjusted only in Heat mode.
9
7
8
4
5
6
Control and Monitoring (Continued)