92
Optional item
Input unit
SEG1
SEG2
SEG3
SEG4
Function of the option
Remarks
Silent mode
Main
0
7
0
0
Disabled (Factory default)
Enables the silent mode for
night-time in cooling mode
(It operates automatically
depending on the
temperature.)
However, if the external contact
interface module (MIM-B14) is
used, entering the silent mode
is available with contact signal
in cooling and heating mode.
(A type PBA : this function is
used in cooling mode.)
0
1
LEVEL 1 / Auto
0
2
LEVEL 2 / Auto
0
3
LEVEL 3 / Auto
0
4
LEVEL 1 / External contact
0
5
LEVEL 2 / External contact
0
6
LEVEL 3 / External contact
High-head
condition setting
Main
0
8
0
0
Disabled (Factory default)
0
1
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
40~80m above the indoor unit
0
2
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is located
over 80m above the indoor unit
0
3
Height difference type 2
(Outdoor unit is lower than
indoor unit)
When indoor unit is over 30 m
above the outdoor unit
Long-piping
condition
setting (Setting
is unnecessary
if high-head
condition is set)
Main
0
9
0
0
Disabled (Factory default)
0
1
LEVEL 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170m
0
2
LEVEL 2
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170m
Energy saving
setting
(A Type PBA)
Main
1
0
0
0
Disabled (Factory default)
0
1
Enabled
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in heating
mode.
Energy control
operation
(B Type PBA)
Main
1
0
0
0
Basic (Factory default)
Energy control option of
designated operation sequence
❋
Operating in energy saving
mode, capacity might
decrease compared to
normal operation mode
0
1
Energy saving
0
2
Power
Rotation defrost
(HR only)
Main
1
1
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous
heating operation is possible
but heating performance will
decrease during rotation defrost
operation
Setting outdoor unit option switch and key function
Summary of Contents for DVM S AM080FXVAGH
Page 112: ......