Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit capacity (kW)
(Cooling)
*Maximum pipe length within 90m
*Maximum pipe length over 90m
Liquid pipe (mm)
gas pipe (mm)
Liquid pipe (mm)
gas pipe (mm)
22.4 kW
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
22.5 kW ~ 28.1 kW
Ø 22.22
Ø 25.40
note1)
28.2 kW ~ 33.6 kW
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
33.7 kW ~ 40.0 kW
40.1 kW ~ 45.0 kW
Ø 31.75
note2)
45.1 kW ~ 50.4 kW
Ø 15.88
Ø 19.05
50.5 kW ~ 56.0 kW
56.1 kW ~ 63.3 kW
63.4 kW ~ 70.3 kW
Ø 34.92
Ø 38.10
note3)
70.4 kW ~ 98.4 kW
Ø 19.05
Ø 22.22
98.5 kW ~ 135.2 kW
Ø 41.28
Ø 41.28
135.3 kW ~ 169.0 kW
Ø 53.98
169.1 kW ~ 252.0 kW
Ø 22.22
Ø 53.98
Ø 25.40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
❇
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe installed on the site,
a socket is provided by default together with the outdoor unit.