8
Preparing for installation
Model name for combination
AM180FXVAGH
AM200FXVAGH
AM220FXVAGH AM240HXVAGH AM260HXVAGH
Number of individual outdoor units
1
1
1
1
1
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
AM140FXVAGH
AM160FXVAGH
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
1
AM240HXVAGH
1
AM260HXVAGH
1
Rated capacity
Cooling (kW)
50.4
56
61.6
67.2
72.8
Heating (kW)
56.7
63
69.3
75.6
81.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
25.2
28
30.8
33.6
36.4
Maximum (kW)
65.5
72.8
80.1
87.4
94.6
Maximum number of connectable
indoor units
32
36
40
43
47
Model name for combination
AM280HXVAGH1 AM300HXVAGH1 AM320HXVAGH1 AM340HXVAGH1 AM360HXVAGH1
Number of individual outdoor units
2
2
2
2
2
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
1
1
1
1
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
1
1
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
78.6
84.0
89.6
95.2
101.6
Heating (kW)
88.2
94.5
100.8
107.1
114.3
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
39.3
42.0
44.8
47.6
50.8
Maximum (kW)
102.2
109.2
116.5
123.8
132.1
Maximum number of connectable
indoor units
51
54
58
61
64