2-42
Samsung Electronics
Outdoor Unit
(cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.
TYPE
New Model
Model
AM240KXVANH/TL AM260KXVANH/TL AM280KXVANH/TL AM300KXVANH/TL AM220KXVJNH/ID
AM240KXVJNH/ID
Mode
HP
HP
HP
HP
HP
HP
Power
Φ, V,
Hz
3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60
Capacity
Horse Power
HP
24
26
28
30
22
24
Cooling
kW
67.2
72.8
78.6
84.0
61.6
67.2
Heating
kW
75.6
81.9
88.2
94.5
69.3
75.6
Power
Power input
(Nominal)
Cooling 1)
kW
17.10
18.91
20.68
22.70
15.50
17.10
Heating 2)
17.42
18.00
20.18
20.59
15.80
17.42
Current
Input
(Nominal)
Cooling 1)
A
27.40
30.30
33.20
36.40
24.80
27.40
Heating 2)
27.90
28.90
32.40
33.00
25.30
27.90
Running
Current
Cooling
A
27.40
30.30
33.20
36.40
24.80
27.40
Heating
A
27.90
28.90
32.40
33.00
25.30
27.90
Max
A
55.0
60.0
67.0
73.0
57.1
63.3
Power
Consump-
tion
Cooling
kW
17.10
18.91
20.68
22.70
15.50
17.10
Heating
kW
17.42
18.00
20.18
20.59
15.80
17.42
MCA/MFA
A
55.0 / 75
60.0 / 75
67.0 / 75
73.0 / 90
57.1 / 75
63.3 / 75
COP
Nominal Cooling
-
3.930
3.850
3.800
3.700
3.970
3.930
Nominal Heating
-
4.340
4.550
4.370
4.590
4.390
4.340
ESEER (HP)
-
-
-
-
-
-
-
Compressor
Model
-
DS-GB066FA*
DS-GB066FA*
DS-GB070FA*
DS4G*5080F*
DS-GB066FA*
DS-GB066FA*
Type
INV x 2EA
INV x 2EA
INV x 2EA
INV x 2EA
INV x 2EA
INV x 2EA
Output
kW
6.39 x 2
6.39 x 2
6.76 x 2
7.81 x 2
6.39 x 2
6.39 x 2
Lubricant
Type
-
PVE
PVE
PVE
PVE
PVE
PVE
Charging
cc
1100 x 2
1100 x 2
1100 x 2
1400 x 2
1100 x 2
1100 x 2
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
12.5
12.5
14.0
14.0
10.0
10.0
Fan
Type
-
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Motor Output
W
620 x 2
620 x 2
620 x 2
620 x 2
620 x 2
620 x 2
Airflow rate
᎑ ͠
ΞΚΟ
340
340
340
340
340
340
Piping
Connections
Liquid pipe
Φ, mm
15.88
19.05
19.05
19.05
15.88
15.88
Φ, inch
5/8"
3/4"
3/4"
3/4"
5/8"
5/8"
Gas pipe
Φ, mm
34.92
34.92
34.92
34.92
28.58
34.92
Φ, inch
1+3/8"
1+3/8"
1+3/8"
1+3/8"
1+1/8"
1+3/8"
High pressure gas pipe
Φ, mm
-
-
-
-
-
-
Φ, inch
-
-
-
-
-
-
Installation
Limitation
Max. Length
m
220
220
220
220
220
220
Max. Height
m
50(110)/40
50(110)/40
50(110)/40
50(110)/40
50(110)/40
50(110)/40
Cable
Main Power(Below 20m)
mm2
-
-
-
-
-
-
Communication
mm2
-
-
-
-
-
-
Set
Dimension
Net weight
kg
333
333
342
350
330.5
330.5
Gross weight
kg
355
355
364
372
352.5
352.5
Net dimension (WxHxD)
mm
1295x1795x765
1295x1795x765
1295x1795x765
1295x1795x765
1295x1795x765
1295x1795x765
Gross dimension (WxHxD)
mm
1363x1987x832
1363x1987x832
1363x1987x832
1363x1987x832
1363x1987x832
1363x1987x832
Operating
Temp. Range
Cooling
ఁ
-5 ~ 48
-5 ~ 48
-5 ~ 48
-5 ~ 48
-5 ~ 54
-5 ~ 54
Heating
ఁ
-25 ~ 24
-25 ~ 24
-25 ~ 24
-25 ~ 24
-25 ~ 24
-25 ~ 24