2-23
Samsung Electronics
TYPE
New Model
Model
AM240HXVAGH
AM260HXVAGH
Mode
HP
HP
Power
Φ, V, Hz
3/AC380~415/50
Capacity
Horse Power
HP
24
26
Cooling
kW
67.2 72.8
btu/h
-
-
Heating
kW
75.6 81.9
btu/h
-
-
Power
Power input
(Nominal)
Cooling 1)
kW
17.10 19.30
Heating 2)
19.80
21.80
Current Input
(Nominal)
Cooling 1)
A
26.83
30.28
Heating 2)
31.06
34.20
Running
Current"
Cooling
A
26.83
30.28
Heating
A
31.06 34.20
Max
A
55
58
Power
Consumption
Cooling
kW
26.83
30.28
Heating
kW
31.06 34.20
MCA/MFA
A
60.5/75
63.8/75
COP
Nominal Cooling
-
3.930
3.772
Nominal Heating
-
3.818
3.757
ESEER (HP)
-
-
-
Compressor
Model
-
DS-GB066FA*
DS-GB070FA*
Type
INV x 2EA
INV x 2EA
Output
kW
-
-
Lubricant
Type
-
FVC68D
FVC68D
Charging
cc
6,200
6,200
Refrigerant
Type
-
R410A
R410A
Factory Charging
kg
14.3
14.3
Fan
Type
-
Pro BLDC
Pro BLDC
Motor Output
W
620 x 2
620 x 2
Airflow rate
᎑ ͠ΞΚΟ
310 310
Piping
Connections
Liquid pipe
Φ, mm
15.88
19.05
Φ, inch
5/8"
3/4"
Gas pipe
Φ, mm
34.92
34.92
Φ, inch
1 3/8"
1 3/8"
High pressure gas pipe
Φ, mm
-
-
Φ, inch
Installation
Limitation
Max. Length
m
200(220)
200(220)
Max. Height
m
110.0(40.0)
110.0(40.0)
Cable
Main Power(Below 20m)
mm2
16
16
Communication
mm2
VCTF 0.75 ~ 1.5(2P)
VCTF 0.75 ~ 1.5(2P)
Set
Dimension
Net weight
kg
360
360
Gross weight
kg
370
370
Net dimension (WxHxD)
mm
1,295 x 1,695 x 765
1,295 x 1,695 x 765
Gross dimension (WxHxD)
mm
1,363 x 1,887 x 832
1,363 x 1,887 x 832
Operating Temp. Range
Cooling
ఁ
-5.0 ~ 48.0
-5.0 ~ 48.0
Heating
ఁ
-25.0 ~ 24.0
-25.0 ~ 24.0
Outdoor Unit
(cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.