Troubleshooting
4-16
Samsung Electronics
■
Diagnosis and Adjustment (Error Code)
►
Error code related to the Communications / Settings / HW
(cont.)
Error mode
Cause
E-346
Error due to operation failure of Fan2
E-347
Motor wire of Fan2 is not connected
E-348
Lock error on Fan2 of outdoor unit
E-353
Error due to overheated motor of outdoor unit's Fan2
E-355
Error due to overheated IPM of Fan2
E-361
Error due to operation failure of inverter compressor 2
E-364
Error due to over-current of inverter compressor 2
E-365
V-limit error of inverter compressor 2
E-366
Error due to over voltage /low voltage of inverter PBA2
E-367
Error due to unconnected wire of compressor 2
E-368
Output current sensor error of inverter PBA2
E-369
DC voltage sensor error of inverter PBA2
E-371
Error due to the INV2 Data Flash
E-374
Heat sink temperature sensor error of inverter PBA2
E-378
Error due to overcurrent of Fan2
E-383
Error due to over current of Fan2
E-385
Error due to input current of inverter 2
E-386
Over-voltage/low-voltage error of Fan2
E-387
Hall IC connection error of Fan2
E-389
V-limit error on Fan2 of compressor
E-391
Error due to the Fan2 DataFlash
E-393
Output current sensor error of Fan2
E-396
DC voltage sensor error of Fan2
E-399
Heat sink temperature sensor error of Fan2
E-400
Error due to overheat caused by contact failure on IPM of Inverter PBA2
E-407
Compressor operation stop due to high pressure protection control
E-410
Compressor operation stop due to low pressure protection control or refrigerant leakage
E-416
Compressor operation stop due to discharge temperature protection control
E-425
Phase reversal or phase failure (3Ø outdoor unit wiring, R-S-T-N ), connection error on 3 phase input
E-428
Compressor operation stop due abnormal compression ratio
E-435
Flow Switch Error
E-436
Error on the Heat exchanger frost protection
E-438
EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI (ESC) EEV
E-439
Error due to refrigerant leakage
E-440
Heating mode restriction due to high air temperature
In case of DVM water, Heating mode restriction due to high water temperature
E-441
Cooling mode restriction due to low air temperature
In case of DVM water, Heating mode restriction due to low water temperature
E-442
Refrigerant charing restriction in heating mode when air temperature is over 15 °C
E-443
Operation prohibited due to low pressure
E-445
CCH is deatched