Product Specifications
2-18
Samsung Electronics
TYPE
New Model
Comparative Model
Model
AM080FXVAGR
AM100FXVAGR
AM120FXVAGR
RD080HRXG
6
RD100HRXG
6
RD120HRXG
6
Mode
HR
HR
HR
HR
HR
HR
Power
Ø,V,Hz
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
Capacity
Horse Power
HP
8
10
12
8
10
12
Capacity
kW
22.4
28.0
33.6 22.4 28.0
33.6
btu/h
76,400
95,500
114,600 76,400 95,500
114,600
Heating
kW
25.2
31.5
37.8 25.2 31.5
37.8
btu/h
86,000 107,500 129,000 86,000 107,500 129,000
Power
Power Input
(Nominal)
Cooling 1)
kW
5.00
6.80
8.40
-
-
-
Heating 2)
5.10
6.70
8.70
-
-
-
Current Input
(Nominal)
Cooling 1)
A
8.00
10.90
13.50
-
-
-
Heating 2)
8.20
10.70
14.00
-
-
-
Running
Current
Cooling
A
8.00
10.90
13.50 8.80 13.00
20.00
Heating
A
8.20
10.70
14.00 11.40 12.70
18.40
Max.
A
18.00
21.10
25.00 18.40 21.50
28.40
Power
Consumption
Cooling
kW
5.00
6.80
8.40 5.20 7.04
9.20
Heating
kW
5.10
6.70
8.70 5.46 6.89
8.50
MCA / MFA
A
22.5 / 30
29.9 / 40
31.3 / 40
-
-
-
COP
Nominal Cooling
-
4.48
4.12
4.00
-
-
-
Nominal Heating
-
4.94
4.70
4.34
-
-
-
ESEER (HP)
7.85
7.25
7.03
-
-
-
Compressor
Model
-
DS-GB052FA****
DS-GB066FA****
DS-GB066FA****
ZPJ61KCE-TFD
ZPI61KCE-TFD
ZPJ61KCE-TFD
ZPI61KCE-TFD
ZPJ83KCE-TFD
ZPI83KCE-TFD
Type
INV x1
INV x1
INV x1
DVI x1 + FVl x1
DVI x1 + FVl x1
DVI x1 + FVl x1
Output
kW
4.70
5.80
5.80
4.36 + 4.36
4.36 + 4.36
5.87 + 5.87
Lubricant
Type
-
FVC68D
FVC68D
FVC68D
3MAF POE
3MAF POE
3MAF POE
Charging
cc
3,900
3,900
3,900 4,370 4,370
4,370
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
5.5
5.2
5.5
5.0
5.0
5.0
FAN
Type
-
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Motor Output
W
400
400
400
630
630
630
Airflow rate
᎑ ͠ΞΚΟ
173
173
210
173
173
210
Pipe
Piping
Connections
Liquid
Ø,mm
9.52
9.52
12.70
9.52
9.52
12.70
Ø,inch
3/8"
3/8"
1/2"
Gas
Ø,mm
19.05
22.22
28.58
19.05
22.22
25.40
Ø,inch
3/4"
7/8"
1 1/8"
Dis. Gas
Ø,mm
15.88
19.05
19.05
15.88
19.05
22.22
Ø,inch
5/8"
3/4"
3.4"
Installation
Limitation
Max.Length
m
200(220)
200(220)
200(220)
200
200
200
Max.Height
m
110(40)
110(40)
110(40)
50(40)
50(40)
50(40)
Cable
Main Power(Below/about20m) mm2
4.0
4.0
4.0 1.5 2.5
4.0
Communication
mm2
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
Set
Dimension
Net Weight
DVM S HP
kg
190.0
190.0
190.0
243
243
243
DVM S HR
195.0
195.0
195.0
Shipping
Weight
DVM S HP
kg
206.0
206.0
206.0
259
259
259
DVM S HR
211.0
211.0
211.0
Net Dimension(WxHxD)
mm
880x1,695x765
880x1,695x765
880x1,695x765
880x1695x765
880x1695x765
880x1695x765
Gross Dimension(WxHxD)
mm
948x1,657x832
948x1,657x832
948x1,657x832
948x1912x832
948x1912x832
948x1912x832
Operating
Temp Range
Cooling
DVM S HP
ఁ
-5.0~48.0
-5.0~48.0
-5.0~48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
DVM S HR
-15.0~48.0
-15.0~48.0
-15.0~48.0
Heating
-20.0~24.0
-20.0~24.0
-20.0~24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20 .0~ 24.0
Outdoor Unit
(cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.