Samsung Electronics
9-3
Heat
Exchanger
(Evaporator)
Heat
Exchanger
(Condenser)
Cooling
Gas leak check point
Liquid pipe
Gas pipe
Compressor
Muffle
Accumulator
3-Way valve
Expansion
valve
Filter
Filter
3-Way valve
Indoor Unit
Outdoor Unit
9-2 Refrigerating Cycle Diagram
Amount of refilling per extension length of 1mm; when extending the pipe length by more
than 7.5m, "A" g of R410 , refrigerant should be refilled per extension length of 1m.
Model
"A" g
UH140GAMC
70g
UH105GAMC
70g
UH070EAMC
40g
UH052EAMC
25g
UH094EAM1C
60g