Troubleshooting
12-3-6 Indoor float switching error
Note
: E3 error should be released when indoor unit power is reset.
No
No
No
No
No
Replace the indoor unit PCB
Replace the drain pump
Replace the drain pump
Replace the indoor unit PCB
Yes
Yes
Yes
Yes
Yes
Yes
Reset the indoor unit power
and check the drain pump operation
Normal operation
Normal operation
Check the floating switch is bad.
Reset the indoor unit
power after replace
Is the resistance value
when measuring the resistance value
of two terminal after taking out the floating
switch connector connected to indoor
unit PCB? (Open status)
Is much the water of drain pan ?
Does the drain pump operate?
Does the water level decrease?
Is the same error occurred?
Is the terminal
voltage of drain pump PCB about
AC220V?
Re-assembly the floating switch
connector and perform the reset of
outdoor power(Required the reset of
indoor unit power)
No
Outdoor unit display
Indoor unit display
How to determine
Reason of error
(
Indoor float switching error )
(Operation) (Timer)
(Airflow)
(Filter)
The status continues over 1 minute that indoor unit float switch is opened.
The rising of water level of drain pan due to the disorder of indoor unit drain pump,
the badness of detection sensor
12-11
Summary of Contents for CH070EAMC
Page 34: ...Samsung Electronics 5 2 Panel 5 4...
Page 44: ...Samsung Electronics 5 4 Ass y Control In CH140EAMC DB93 04137A 5 14...
Page 46: ...Samsung Electronics CH105EAMC DB93 04376A Exploded Views and Parts List 5 16...
Page 48: ...Samsung Electronics CH052 070 094EAMC DB93 05254A Exploded Views and Parts List 5 18...
Page 54: ...Samsung Electronics UH052 070EAMC DB93 04731B DB98 04731A Exploded Views and Parts List 5 24...
Page 76: ...Samsung Electronics 7 8 MEMO...
Page 89: ...Samsung Electronics 10 8 MEMO...
Page 125: ...Samsung Electronics 14 10 MEMO...