Samsung Electronics
94
Troubleshooting
4-3-11 Setup Error for MCU Branch part – Setup Error for MCU Quantity Used
1. Inspection Method
Check the Main PBA MCU quantity setting switch of the outdoor unit and check the installed MCU quantity matches. Check whether
each MCU PBA address switch was duplicated.
To use, reset by pressing the K3 button of the outdoor unit after the reset is completed, or reset after turning off the power and then
turn it on again.
Outdoor Unit PBA
Quantity of
Indoor Unit
Quantity of
MCU
Indoor Unit: -
MCU: 2
Address: 0
Address: 1
Address: 2
Outdoor Unit PBA
Quantity of
Indoor Unit
Quantity of
MCU
Indoor Unit:- MCU: 3
Branch
Branch
Branch
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation Defrost Timer
Fan
Filter/
MPI
Operation Defrost Timer
Filter Operation Timer Turbo
24
℃
27
℃
×
×
◑
◑
×
×
◑
◑
×
×
×
◑
◑
×
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
• Occurs when the quantity of MCU is incorrectly set by the outdoor unit.
• Occurs when same addresses are found when two or more MCU are connected.
Cause of
problem
• Outdoor unit MCU setup and same address errors when connecting two or more MCUs .
4-3 Appropriate Measures for Different Symptom
(cont.)
•
Example of MCU quantity setting error
ex) PBA MCU setting quantity of outdoor unit = 2 / MCU installed Quantity = 3
• Example of MCU address setting error
ex) Two among three of MCU address was set to 0
Summary of Contents for AM080FXWANR
Page 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Push buttons Type...
Page 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont DIP S W Type...
Page 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB AC...
Page 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont DC...