Troubleshooting
Samsung Electronics
111
4-3-27 EVI In Temperature sensor error (Open/Short)
1. Cause of problem
Outdoor EVI IN
sensor connector (CN44) connected
to PBA?
Is the resistor value matching with
“NOTE1” table?
Separate the connector of the Outdoor EVI In
Temperature sensor from the PBA and measure
the resistance value between the 2 terminals.
Restart operation after replace the PBA
Restart operation after connecting
the connector to PBA
Replace this part as it is the defective of the
Outdoor EVI In Temperature sensor itself.
No
No
Yes
Yes
Resistance value measure part
EVI-IN
EVI-IN
CN44 (3, 4)
NOTE1
Temperature(°C)
Resistance(KΩ)
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI
Operation
Defrost
Timer
Filter
Operation
Timer
Turbo
×
×
◑
◑
◑
×
◑
◑
◑
●
◑
◑
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
∙ Detect according to temperature detected with the EVI-In pipe temperature thermistor.
Cause of
problem
∙ EVI-In temperature sensor is defective. (open/short)
4-3 Appropriate Measures for Different Symptom
(cont.)
Summary of Contents for AM080FXWANR
Page 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Push buttons Type...
Page 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont DIP S W Type...
Page 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB AC...
Page 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont DC...