Troubleshooting
Samsung Electronics
69
غ
Auto Trial Operation
ـ͑
After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling
Heating
Method of Entry
K2 Tact Switch twice
K1 Tact Switch twice
Compressor
Normal operation, but the maximum frequency limit (differ by model)
Indoor Unit
Whole operation (The set temperature=3
π
C)
Whole operation (The set temperature=40
π
C)
Other Actuators
Normally control conduct
Operation time
Min : 60 minutes, Max : 10 hours
Etc.
∙ Exceed the maximum operating time at stops and waits.
∙ Protection and control, self-diagnosis is performed.
غ
Refrigerant filling operation
ـ
Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling
Heating
Method of Entry
K2 Tact Switch one time
K1 Tact Switch one time
Compressor
Starting frequency (Mild Start frequency) operation
Indoor Unit
Whole operation (The set temperature=3
π
C)
Whole operation (The set temperature=40
π
C)
Other Actuators
Normally control conduct
Operation time
60 minutes
Etc.
During the filling operation does not enter the special operation, such as oil recovery.
4-2 Service Operation
(cont.)
4-2-1 Special Operation
(cont.)
Summary of Contents for AM080FXWANR
Page 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Push buttons Type...
Page 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont DIP S W Type...
Page 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB AC...
Page 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont DC...