Troubleshooting
Samsung Electronics
151
4-4-7 Case study – E206 (Internal communication error of the outdoor unit C-box)
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation Defrost Timer
Fan
Filter/
MPI
Operation Defrost Timer
Filter Operation Timer Turbo
24
℃
27
℃
×
×
◑
◑
×
×
◑
◑
×
×
×
◑
◑
×
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
∙ PBA does not respond to the invoked Main PBA
Cause of
problem
∙ C-Box internal Inverter PBA, Fan PBA, Hub PBA defective
Possibility
1) Poor connection of communication wiring and connector
2) Defect of related electric component
* Reference
E206- C001 : HUB PBA communication error / E206-C002 : FAN PBA communication error
E206- C003 : INV1 PBA communication error / E206-C004 : INV2 PBA communication error
E206- C005 : Water Hub PBA communication error
Main PBA
Hub PBA
Inverter PBA