37
ENGLISH
Setting Main Address
The MAIN address is for communication between the
indoor unit and the outdoor unit. Therefore, you must
set it to operate the air conditioner properly.
You can set the MAIN address from ‘00’ to ‘99’ by mixing
SW01 and SW02. The MAIN address from ‘00’ to ‘99’
should differ from each other.
Check the indoor unit address on the plan that you are
to install and set the address according to the plan.
You may not need to set main address if you selected
Auto Address Setting from the outdoor unit: see details
on the outdoor unit installation manual.
Note
For Example
When MAIN address is set as “12”.
Setting RMC Address
The SW03 and SW04 RMC switch is the address setting
switch for controlling the indoor unit with the centralized
controller.
You must set the SW03, SW04 and K2 switch when using
the centralized controller.
You don’t have to set the SW03 and SW04 RMC switch
when not using the centralized controller.
SW03
SW04
For Example
When RMS address is set as “12”.
1.
Before installing the indoor unit, assign an address to the
indoor unit according to the air conditioning system plan.
2.
The address of the indoor unit is assigned by adjusting
MAIN(SW01, SW02) and RMC(SW03, SW04) rotary
switches.
※
The designs and shape are subject to change according to the
model.
AM
FBFDEH
Series
Setting the function switch
Switch No.
Function
ON
OFF
SW05
K1 -
-
-
K2 Centralized control
Do not use
Use
K3 RPM compensation
-
-
K4 Drain pump
-
-
SW06
K5 Revised room tempera-
ture in heat mode
-
-
K6 Filter clean indicator
1000 hours
2000 hours
K7 Hot water coil
-
-
K8 Electric heater
-
-
SW07
K9
Minimum opening of
stopped EEV during
heating
Fixed 80 step
0 or
80 step
K10
Displaying status of
wireless remote
controller
Do not use
Use
K11 External control
Do not use
Use
K12 -
-
-
AM
FBFDEH
Series
NASA_Floor Stand_AM@@@FNFDEH@_IB,IM_EN_03677A-05.indd 37
2016-04-06 오후 2:25:23