Installation Part

Selecting the Installation Location

Preparing for installation

Decide the installation location, with the consideration of the 

following conditions, under user’s approval.

Refrigerant pipe work must be done before installing the indoor 

unit.

Place where air flow is not disturbed.

Place with flat surface and where structure can bear the 

weight and vibration of the indoor unit. (If the structure 

is not strong enough, indoor unit may fall and get  

damaged or cause personal injury.)

Place where sufficient space can be guaranteed for  

maintenance and other services.

Place where condensation can be drained easily.

Place that allows refrigerant pipe connection within 

allowable distance.

Place where indoor unit will not be exposed to direct 

sunlight.

Place that can keep the distance of at least 1m between 

power/communication cable and any electronic devices. 

(Depending on the circumstances, problem may occur 

even if you secure 1m of distance.)

1.

Check the product and the location where it will be installed.

2.

Check the required installation conditions.

3.

Drill a hole on a floor or a wall and insert bolt anchors as shown  

in the figure.

-  Use a Φ9.52 or M10  

 bolts for installation.

-  At least 2 anchor bolts  

 must be used for fixing  

 the indoor unit.

1.

Select a location with no obstacles in surrounding area while allowing 

easy pipe and electrical installation, and also consider a place where it 

may not fall or get shaken by vibration or any other external force.

2.

Drill a hole for the drain on the bottom or rear side of the 

indoor unit with a diameter between 60~65mm.

3.

Make sure that product is in level.

-  Check the horizontality by using a level or a vinyl tube  with water etc.

•   

If the indoor unit is not installed in level, drain water may get in 

to the indoor unit due to incorrect measurement of water level.

4.

Fix the indoor unit by connecting it to the anchor bolt.

(Unit: mm)

‘A’ or mor

e

60 or more

Air inlet

Air outlet

Air filter

60

50 or below

Cover

Model

A



036



700



056



980



071



980

Concrete

Hole for 

anchor  

or plug

Fixing bolt (Φ9.52 or M10)

•  All the part must be purchased separately.

 

•  Service space must be secured.

Indoor unit installation

Purging the Unit

  The designs and shape are subject 

to change according to the  model.

On delivery, the indoor unit is loaded with inert gas. All this gas 

must therefore be purged before connecting the assembly  

piping. To purge the inert gas, proceed as follows.

Unscrew the pinch pipe at the end of each refrigerant pipe.

Result: 

   All inert gas escapes from the indoor unit.

Liquid 

refrigerant 

port

Gas 

refrigerant 

port

No.

Name

Description

Liquid pipe connection



036/056



 : ø6.35



071



 : ø9.52

Gas pipe connection



036/056



 : ø12.7



071



 : ø15.88

Drain pipe connection

ID ø18

Power wiring

-

Air intake

-

Air outlet

-

Model

"A"

"B"

"C"



036



945 mm

730 mm

700 mm



056/071



1225 mm

1010 mm

980 mm

To prevent dirt or foreign 

objects from getting into the 

pipes during installation, do 

NOT remove the pinch pipe 

completely until you are ready to 

connect the piping.

Note

NASA_Floor Stand_AM@@@FNFDEH@_IB,IM_EN_03677A-05.indd   21

2016-04-06   오후 2:25:13

Summary of Contents for AM***FNFDEH series

Page 1: ...magine the possibilities Thank you for purchasing this Samsung product Floor Standing Unit AM FNFDEH AM FBFDEH IT FR ES EN PT NL EL DE HU PL DB68 03677A 06 NASA_Floor Stand_AM FNFDEH _IB IM_EN_03677A...

Page 2: ...e summer but can also be an efficient heating method in the winter with the advanced Heat pump system This technology is up to 300 more efficient than electrical heating so you can further reduce its...

Page 3: ...m Important safety symbols and precautions WARNING Hazards or unsafe practices that may result in severe personal injury or death CAUTION Hazards or unsafe practices that may result in minor personal...

Page 4: ...cable Do not yank the power cable and touch the power plug with hands Potential risk of fire or electric shock Never use a damaged or dusted power plug power cable or loosened power receptacle Potent...

Page 5: ...itioner Improper installation carries a risk of unit malfunction water leakage electric shock or fire If installing in specialty areas such as a factory complex or saline coastal area consult the plac...

Page 6: ...ube When opening or closing the front panel use a stable stool and watch your steps carefully Disconnect the air conditioner from power supply before it is repaired or disassembled Clean the air condi...

Page 7: ...r should not flow directly towards people pets and plants It is harmful to your health pets and plants Do not drink drain water coming out of the air conditioner Potential risk of health hazard Do not...

Page 8: ...nditioner is working turn off the power source immediately Max current is measured according to IEC standard for safety and current is measured according to ISO standard for energy efficiency Check fo...

Page 9: ...with the appliance For use in Europe This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowl...

Page 10: ...lations in force with slings trucks scaffolding or any other means of elevation won t be considered in warranty and charged to end user Ensure the off on and protection switches are properly installed...

Page 11: ...the product and its electronic accessories e g charger headset USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environm...

Page 12: ...l or warm with optimal efficiency Please read the user manual to get started and to make the best use of the air conditioner Floor Standing Unit Your air conditioner may look slightly different from t...

Page 13: ...air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air condi...

Page 14: ...Washable air filter captures large particles from the air The filter is cleaned with a vacuum or by hand washing 1 Unscrew the screws 8 on the top of the indoor unit 2 Remove the front cabinet by unsc...

Page 15: ...deformed when it is exposed to direct sunlight 6 Press the Filter Reset button on the remote controller Clean the Air filter every 2 weeks or when the filter indicator lights up on the remote control...

Page 16: ...pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat...

Page 17: ...ttery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the c...

Page 18: ...change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the r...

Page 19: ...he floor HEATING 27 C or less 20 C to 24 C Internal protection triggers and the air conditioner will stop DRYING 18 C to 32 C 5 C to 48 C Condensation may occur on the indoor unit with risk to have ei...

Page 20: ...DEH EU 23 0 kg 945 220 600 mm AM056FBFDEH EU 28 5 kg 1225 220 600 mm AM071FBFDEH EU 28 5 kg 1225 220 600 mm Indoor unit NASA AM036FNFDEH EU 23 0 kg 945 220 600 mm AM056FNFDEH EU 28 5 kg 1225 220 600 m...

Page 21: ...not fall or get shaken by vibration or any other external force 2 Drill a hole for the drain on the bottom or rear side of the indoor unit with a diameter between 60 65mm 3 Make sure that product is i...

Page 22: ...installer to pressurize the whole system with nitrogen using a pressure regulator at a pressure above 4 1MPa gauge Leak test Performing LeakTest Insulation Discharge all the nitrogen to create a vacuu...

Page 23: ...m entering Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hang...

Page 24: ...se Circuit Breaker ELB Earth Leakage Breaker 3 The power cable should be used only copper wires 4 Connect the power cable 1 L 2 N among the units within maximum length and communication cable F1 F2 ea...

Page 25: ...aximum length within 10 power drop among indoor units Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running c...

Page 26: ...etting status select the option as listed below Option setting is available from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18...

Page 27: ...6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each tim...

Page 28: ...Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mo...

Page 29: ...0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE SettingRMCaddress Groupchannel 16 Groupaddress Remote...

Page 30: ...rs using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEVStepofstoppedunit duringoilre...

Page 31: ...ps Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 Disuse 0 Disuse 0 Default value...

Page 32: ...r SEG15 3 you need to use an external sensor or wired remote controller sensor to detect indoor temperature exactly 4 Default setting value 4Way Cassette Mini 4Way Cassette 5 C Other indoor units 2 C...

Page 33: ...lectronicheaterintheflowchanneloftheindoorunitfan Air Flow Suction side Discharge side Electronic heater should not be installed Duct Indoor unit 05 series installation option SEG1 SEG2 SEG3 SEG4 SEG5...

Page 34: ...C 1 0 5 C 1 1 5 C 2 1 C 2 1 C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE...

Page 35: ...thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room temp set temp f heating compensation temp External heater is turned on...

Page 36: ...edvalue Indication 0 D 2 1 7 1 When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setti...

Page 37: ...en using the centralized controller You don t have to set the SW03 and SW04 RMC switch when not using the centralized controller SW03 SW04 For Example When RMS address is set as 12 1 Before installing...

Page 38: ...fy operatora www samsung com pl support IRAN 021 8255 www samsung com iran support HUNGARY 0680SAMSUNG 0680 726 786 0680PREMIUM 0680 773 648 www samsung com hu support SAUDI ARABIA 800 247 3457 800 24...

Reviews: