![Samsung AM***FNFDEH series User Manual Download Page 30](http://html1.mh-extra.com/html/samsung/am-fnfdeh-series/am-fnfdeh-series_user-manual_4747059030.webp)
30
Setting an indoor unit address and installation option(Continued)
1.
Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2.
The panel(display) should be connected to an indoor unit to receive option.
3.
Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is
“020010-100000- 200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an
indoor unit individually when there is more than one indoor unit.
4.
Set the indoor unit option by wireless remote controller.
Setting an indoor unit installation option (suitable for the condition of each installation location)
Indoor Unit
1(L)
F2
F1
2(N)
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
External room
temperature sensor /
Minimizing fan operation
when thermostat is off
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
Hot water heater
-
EEV Step when
heating stops
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control output /
External heater On or Off
signal
S-Plasma ion
Buzzer
Number of hours
using filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation / Removing
condensated water in
heating mode
EEV Step of stopped unit
during oil return/defrost
mode
Motion detect sensor
-
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to ‘USE + 3minute delay’ even if the drain pump is set to 0.
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to ‘1000hour’ even if the SEG18 is set to
except for 2 or 6.
When setting the option other than above SEG values, the option will be set as “0”.
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central control
option as 0 (Disuse) to exclude the indoor unit from the central control.
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
F4
F3
F1 F2
V2
V1
1(L) 2(N)
2
1
HOT
COIL
AC
POWER
OUTDOOR
COMMUNICATION
Wire Remote
Controller
DC 12 V
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)
COM1
COM2
(+)
L
N
(-)
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
02 series installation option
NASA_Floor Stand_AM@@@FNFDEH@_IB,IM_EN_03677A-05.indd 30
2016-04-06 오후 2:25:20