311
※ In case you want more information about the controllers and accessories, please refer to the Controller and Accessory TDB
on pvi.Samsung.com site or Global Partner Portal site.
13. Installation
Norminal
dimensions
for cable
(mm²)
Norminal
dimensions
for screw
(mm)
B
D
d1
E
F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
Min.
(mm)
Max.
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
1.5
4
6.6
±0.2
3.4
+0.3
-0.2
1.7
±0.2
4.1
6
16
4.3
+0.2
0
0.7
4
8
2.5
4
6.6
±0.2
4.2
+0.3
-0.2
2.3
±0.2
6
6
17.5
4.3
+0.2
0
0.8
4
8.5
4
4
9.5
±0.2
5.6
+0.3
-0.2
3.4
±0.2
6
5
20
4.3
+ 0.2
0
0.9
Outdoor-to-indoor power terminal specifications
•
Connect the cables to the terminal board using the
compressed ring terminal.
•
Cover a solderless ring terminal and a connector part
of the power cable and then connect it.
Silver solder
•
Connect the rated cables only.
•
Connect using a driver which is able to apply the
rated torque to the screws.
• If the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal
may be damaged.
Tightening torque (kgf • cm)
M4
12.0 to 18.0
M5
20.0 to 30.0
•
1N · m = 10 kgf · cm
CAUTION
•
When connecting cables, you can connect the cables
to the electrical part or connect them through the
holes below depending on the spot.
•
Connect the communication cable between the
indoor and outdoor units through a conduit to protect
against external forces, and feed the conduit through
the wall together with refrigerant piping.
•
Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such
as rubber and so on.
•
Must keep the cable in a protection tube.
•
Keep distances of 50mm or more between power
cable and communication cable.
•
When the cables are connected through the hole,
remove the Plate bottom.