12. Capacity Table
Combination
(Capacity Index)
Combination
(Total)
Combination
(%)
Outdoor
Temperature
(℃,DB)
Indoor Temperature(℃, DB)
14
16
18
20
21
22
24
TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW)
2500 2500 3500 3500
12000
150%
-15
5.32
1.69
5.16
1.72
5.01
1.74
4.88
1.76
4.82
1.77
4.77
1.78
4.68
1.79
-10
6.38
1.78
6.20
1.81
6.04
1.83
5.90
1.85
5.84
1.86
5.78
1.87
5.68
1.89
-5
7.43
1.87
7.25
1.90
7.08
1.92
6.93
1.95
6.86
1.96
6.80
1.97
6.69
1.98
0
8.49
1.96
8.29
1.99
8.12
2.01
7.96
2.04
7.88
2.05
7.82
2.06
7.70
2.08
2
8.91
1.99
8.71
2.02
8.53
2.05
8.37
2.07
8.29
2.08
8.22
2.09
8.10
2.11
7
9.97
2.08
9.76
2.11
9.57
2.14
9.30
2.13
9.32
2.18
9.24
2.19
9.11
2.21
10
10.61 2.13 10.39 2.16 10.20 2.19 10.02 2.22
9.94
2.23
9.86
2.24
9.72
2.26
15
11.67 2.22 11.44 2.25 11.24 2.28 11.05 2.31 10.96 2.32 10.88 2.33 10.73 2.35
NOTE
•
Cooling capacity is based on 27°CDB / 19°CWB (indoor temperature), 35°CDB (outdoor temperature).
•
Heating capacity is based on 20°CDB (indoor temperature), 7°CDB/6°CWB (outdoor temperature).
•
The above is the value for connecting with the following indoor units.
- 2000, 2500, 3500, 5000, 6800W class : AR07TXFCAWKNEU, AR09TXFCAWKNEU, AR12TXFCAWKNEU,
AR18TXEAAWKNEU, AR24TXEAAWKNEU
•
Capacities are based on the following conditions:
- Corresponding refrigerant piping length : 5m / - Level difference : 0m
•
The total ability of connected a indoor unit is up to 12kW
•
It is impossible to connect the indoor unit for one room only.
•
This data is reference data for temperature capacity trend.